Section 8
8.1

Breaker close/trip circuit monitoring TCSSCBR

8.1.1

Identification

Function description
Breaker close/trip circuit monitoring
8.1.2

Functionality

The trip circuit supervision function TCSSCBR is designed to supervise the control circuit of the
circuit breaker. The trip circuit supervision generates a current of approximately 1 mA through the
supervised control circuit. The validity supervision of a control circuit is provided for power output
contacts T1, T2 and T3.
The trip circuit supervision operates after a settable definite operating time and resets after a settable
definite time when the fault disappears.
8.1.3

Function block

GUID-6F85BD70-4D18-4A00-A410-313233025F3A V2 EN-US
Figure 33:
8.1.4

Signals

Table 22:
Name
TCS_STATE
BLOCK
Table 23:
Name
ALARM
Technical Manual

Secondary system supervision

Function block
TCSSCBR Input signals
Type
Default
BOOLEAN
BOOLEAN
TCSSCBR Output signals
Type
BOOLEAN
© 2021 Hitachi Energy. All rights reserved.
IEC 61850
IEC 60617
identification
identification
TCSSCBR
-
Description
0
Trip circuit fail indication from I/O-card
0
Block of function
Description
Trip circuit fault indication
Section 8
Secondary system supervision
GUID-C6367ACC-A594-4C2C-B75A-8A62387117BB v5
ANSI/IEEE C37.2
device number
-
GUID-EE8A480D-59AB-423D-9567-317A111EF846 v9
GUID-3F512745-A836-459E-99B6-DC0D0EBFB849 v4
GUID-17411B12-9FC3-4E47-87D1-147BD838FE7D v1
PID-1837-INPUTSIGNALS v14
PID-1837-OUTPUTSIGNALS v14
65