Section 5
Local HMI
5.5.5

Settings

Table 15:
LEDGEN Non group settings (basic)
Name
Operation
tRestart
tMax
Table 16:
GRP1_LED1 Non group settings (basic)
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
5.5.6

Operation principle

5.5.6.1

Operating modes

Collecting mode
LEDs that are used in collecting mode of operation are accumulated (latched on) continuously until
the unit is acknowledged manually. This mode is suitable when the LEDs are used as a simplified
alarm system.
Re-starting mode
In the re-starting mode of operation each new start resets all previous active LEDs and activates only
those, which appear during one disturbance. Only LEDs defined for re-starting mode with the latched
sequence type 6 (LatchedReset-S) will initiate a reset and a restart at a new disturbance. A
disturbance is defined to end a settable time after the reset of the activated input signals or when the
maximum time limit has elapsed.
5.5.6.2

Acknowledgment/reset

From local HMI
Active indications can be acknowledged/reset manually. Manual acknowledgment and manual reset
have the same meaning and refer to a common signal for all the operating sequences and LEDs.
The function is positive edge triggered, not level triggered. Acknowledgment/reset is performed via
the
46
Values (Range)
Unit
Off
-
On
0.0 - 100.0
s
0.0 - 100.0
s
Values (Range)
Unit
Follow-S
-
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
0 - 18
-
0 - 18
-
0 - 18
-
0 - 18
-
button and menus on the LHMI.
© 2021 Hitachi Energy. All rights reserved.
Step
Default
-
Off
0.1
0.0
0.1
0.0
Step
Default
-
Follow-S
1
G1L01_OFF
1
G1L01_RED
1
G1L01_YELLOW
1
G1L01_GREEN
1MRK 511 557-UEN Rev. A
D0E5683T201305151403 v1
Description
Operation Off/On
Defines the disturbance length
Maximum time for the definition of a
disturbance
D0E5680T201305151403 v1
Description
Sequence type for LED 1, local HMI
alarm group 1
Label string shown when LED 1, alarm
group 1 is off
Label string shown when LED 1, alarm
group 1 is red
Label string shown when LED 1, alarm
group 1 is yellow
Label string shown when LED 1, alarm
group 1 is green
D0E5634T201305151403 v1
D0E5635T201305151403 v1
Technical Manual