Settings And Parameters - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 12
Monitoring
Name
WROPCNTLX
ALOPCNTLX
WRABLLX
ALABLLX
ALOPTMLX
UNSTOPOLX
OPERWALLX
ALOUTLX
CRDACOPLX
TMPOUT
12.18.5

Settings and parameters

Table 257: ACBMSCBR Non group settings (basic)
Name
Operation
PhaseIdentifier
ScatterMechCl
Ablation
InitialOpCnt
GlobalBaseSel
Table 258: ACBMSCBR Group settings (basic)
Name
FeedbackSigC
FeedbackSigO
BetaAdjustElec
BetaAdjustMech
MechMonitor
AuxPosAvailable
InitArcTime
Table continues on next page
268
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
INTEGER
REAL
Values (Range)
Unit
Off
-
On
L1
-
L2
L3
0.00 - 3.00
ms
Disable
-
Enable
0 - 20000
-
1 - 6
-
Values (Range)
Unit
Current
-
Load voltage
None
Current
-
Load voltage
None
0.0 - 1.0
-
0.0 - 1.0
-
Disable
-
Enable
None
-
NO
NC
NO and NC
0.0 - 20.0
ms
© 2021 Hitachi Energy. All rights reserved.
Description
Warning: number of operations exceeding set level for this phase
Alarm: number of operations exceeding set level for this phase
Warning: contact ablation exceeding threshold for this phase
Alarm: contact ablation exceeding threshold for this phase
Alarm: CB operating time exceeding threshold for this phase
Unstable mechanical operating times detected for this phase
Too many consecutive operations with monitored value outside
warning limit for this phase
General monitoring alarm for this phase
Coordination output from ACBMSCBR to OPLOG for this phase
Temperature output
Step
Default
-
On
-
L1
0.05
1.00
-
Disable
1
0
1
1
Step
Default
-
Current
-
Current
0.1
0.5
0.1
0.2
-
Disable
-
None
0.1
5.0
1MRK 511 557-UEN Rev. A
Description
Operation mode Off / On
Phase identification of this function
instance
Mechanical closing time scatter of CB
Enable / Disable ablation calculation
Initial mechanical operation count
Selection of global base values group
Description
Feedback signal for detecting actual
switching instants for a close operation
Feedback signal for detecting actual
switching instants for an open operation
Adaptive correction factor applied to
electrical target error
Adaptive correction factor applied to
mechanical target error
Enable / Disable monitoring of
mechanical parameters
Availability of NO / NC auxiliary contact
status
Initial arcing time for re-ignition free de-
energization
Technical Manual