Settings; Monitored Data; Operation Principle - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
Table 199: L4UFCNT Output signals
Name
ERROR
OVERFLOW
LIMIT1
LIMIT2
LIMIT3
LIMIT4
VALUE
12.3.5

Settings

Table 200: L4UFCNT Group settings (basic)
Name
Values (Range)
Operation
CountType
CounterLimit1
CounterLimit2
CounterLimit3
CounterLimit4
MaxValue
OnMaxValue
InitialValue
12.3.6

Monitored data

Table 201: L4UFCNT Monitored data
Name
VALUE
12.3.7

Operation principle

Limit counter (L4UFCNT) counts the number of positive and/or negative flanks on the binary INPUT
signal depending on the function settings. L4UFCNT also checks if the accumulated value is equal or
greater than any of its four settable limits. The four limit outputs will be activated relatively on reach of
each limit and remain activated until the reset of the function.
The counter value is stored in flash memory once per hour and will not be lost at auxiliary power
interruption.
Technical Manual
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
INTEGER
Unit
Off
-
On
Set
-
Reset
Both
1 - 65535
-
1 - 65535
-
1 - 65535
-
1 - 65535
-
1 - 65535
-
Stop
-
Rollover Steady
Rollover Pulsed
0 - 65535
-
Type
INTEGER
© 2021 Hitachi Energy. All rights reserved.
Description
Error indication on counter limit and/or initial value settings
Overflow indication on count of greater than MaxValue
Counted value is larger than or equal to CounterLimit1
Counted value is larger than or equal to CounterLimit2
Counted value is larger than or equal to CounterLimit3
Counted value is larger than or equal to CounterLimit4
Counted value
Step
Default
-
Off
-
Set
1
100
1
200
1
300
1
400
1
500
-
Stop
1
0
Values (Range)
Unit
-
-
PID-3366-OUTPUTSIGNALS v1
Description
Operation Off / On
Select counting on positive and/or
negative flanks
Value of the first limit
Value of the second limit
Value of the third limit
Value of the fourth limit
Maximum count value
Select if counter stops or rolls over after
reaching maxValue with steady or pulsed
overflow flag
Initial count value after reset of the
function
PID-3366-MONITOREDDATA v1
Description
Counted value
GUID-56D7A70E-C5AC-43E1-9586-3601E8B68763 v2
GUID-A6DDEA5C-F356-481B-A442-8C9B7CE5A8C1 v2
Section 12
Monitoring
PID-3366-SETTINGS v1
181