1MRK 511 557-UEN Rev. A
Description
•
Radiated, amplitude-
modulated
Fast transient disturbance tests
•
Communication ports
•
Other ports
Surge immunity test
•
Communication ports
•
Other ports
•
Power supply
Power frequency (50 Hz) magnetic
field
•
3 s
•
Continuous
Pulse magnetic field immunity test
Damped oscillatory magnetic field
Power frequency immunity test
•
Common mode
•
Differential mode
Voltage dips and short
interruptionsc on DC power supply
Voltage dips and interruptions on
AC power supply
Electromagnetic emission tests
•
Conducted, RF-emission
(mains terminal)
0.15...0.50 MHz
Table continues on next page
Technical Manual
Type test value
20 V/m (rms), f=80...1000 MHz and
f=1.4...2.7 GHz
4 kV
4 kV
1 kV line-to-earth
2 kV line-to-earth, 1 kV line-to-line
4 kV line-to-earth, 2 kV line-to-line
1000 A/m
100 A/m
1000 A/m
100 A/m, 100 kHz and 1 MHz
300 V rms
150 V rms
Dips:
40%/200 ms
70%/500 ms
Interruptions:
0...50 ms: No restart
0...∞ s : Correct behaviour at power
down
Dips:
40% 10/12 cycles at 50/60 Hz
70% 25/30 cycles at 50/60 Hz
Interruptions:
0...50 ms: No restart
0...∞ s: Correct behaviour at power
down
<79 dB(µV) quasi peak
<66 dB(µV) average
© 2021 Hitachi Energy. All rights reserved.
Technical data
Reference
IEC 61000-4-3, level 3
IEC 60255-22-3
ANSI C37.90.2-2004
IEC 61000-4-4
IEC 60255-22-4, class A
ANSI C37.90.1-2012
IEC 61000-4-5
IEC 60255-22-5
IEC 61000-4-8, level 5
IEC 61000-4-9, level 5
IEC 61000-4-10, level 5
IEC 60255-22-7, class A
IEC 61000-4-16
IEC 60255-11
IEC 61000-4-11
IEC 60255-11
IEC 61000-4-11
EN 55011, class A
IEC 60255-25
ANSI C63.4, FCC
Section 17
437