1MRK 511 557-UEN Rev. A
Table 299: Wiring error codes
Command
issued to
phase
L1
L2
L3
L1
L1
L1
L1
L1
L1
L2
L2
The indications for dynamic wiring errors will remain active for one task time only.
Command Errors
Whenever CBLEARN receives an invalid command, CMDER is set high. The identified error is
indicated on the CMDERCD output, see
Table 300: Command Error codes
Present state
Breaker is Open
Breaker is Closed
Close operation is in
progress
Table continues on next page
Technical Manual
Status changeover
Description
observed
L1
L2
L3
No
No
No
Command issued to phase L1
but status changeovers are not
received
No
No
No
Command issued to phase L2
but status changeovers are not
received
No
No
No
Command issued to phase L3
but status changeovers are not
received
No
Yes
No
Command issued to phase L1
but status changeovers are
observed in phase L2
No
No
Yes
Command issued to phase L1
but status changeovers are
observed in phase L3
No
Yes
Yes
Command issued to phase L1
but status changeovers are
observed in phases L3 and L2
Ye
Yes
No
Command issued to phase L1
s
but status changeovers are
observed in phases L1 and L2
Ye
No
Yes
Command issued to phase L1
s
but status changeovers are
observed in phases L1 and L3
Ye
Yes
Yes
Command issued to phase L1
s
but status changeovers are
observed in all three phases
No
No
Yes
Command issued to phase L2
but status changeovers are
observed in phase L3
No
Yes
Yes
Command issued to phase L2
but status changeovers are
observed in phases L2 and L3
Command received Error code for CMDERCD
Open command
Close command
Open command
© 2021 Hitachi Energy. All rights reserved.
WIERCD
8
8
8
9
9
9
9
9
9
9
9
Table
300.
CmdErrOpen
CmdErrClose
CmdErrOpenProg
Section 12
Monitoring
wiringErrorStatus
WIERL1
WIERL2
WIERL3
1
0
0
0
1
0
0
0
1
1
1
0
1
0
1
1
1
1
1
1
0
1
0
1
1
1
1
0
1
1
0
1
1
Description for CMDERCD
Function received OPEN command
from the user when CB is in open
position
Function received CLOSE
command from the user when CB is
in closed position
Function received OPEN command
from the user when close operation
of CB is still in progress
341