Hitachi Relion 650 Series Technical Manual page 256

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 12
Monitoring
Table 250: MONALM Group settings (basic)
Name
Inp1LimitSelect
Inp1HystAbsolute
Inp1HiHiLimit
Inp1HiLimit
Inp1LoLimit
Inp1LoLoLimit
Inp1SensorMode
Inp2LimitSelect
Inp2HystAbsolute
Inp2HiHiLimit
Inp2HiLimit
Inp2LoLimit
Inp2LoLoLimit
Inp2SensorMode
Inp3LimitSelect
Inp3HystAbsolute
Table continues on next page
250
Values (Range)
Unit
Disabled
-
Hi, HiHi, Lo, LoLo
Hi, Hi-Hi
Lo, Lo-Lo
Hi, Lo
Hi-Hi, Lo-Lo
Hi
Hi-Hi
Lo
Lo-Lo
0.0 - 99999.9
-
-99999.9 - 99999.9
-
-99999.9 - 99999.9
-
-99999.9 - 99999.9
-
-99999.9 - 99999.9
-
1 sensor mode
-
3 sensor mode
Disabled
-
Hi, HiHi, Lo, LoLo
Hi, Hi-Hi
Lo, Lo-Lo
Hi, Lo
Hi-Hi, Lo-Lo
Hi
Hi-Hi
Lo
Lo-Lo
0.0 - 99999.9
-
-99999.9 - 99999.9
-
-99999.9 - 99999.9
-
-99999.9 - 99999.9
-
-99999.9 - 99999.9
-
1 sensor mode
-
3 sensor mode
Disabled
-
Hi, HiHi, Lo, LoLo
Hi, Hi-Hi
Lo, Lo-Lo
Hi, Lo
Hi
Hi-Hi
Lo
Lo-Lo
0.0 - 99999.9
-
© 2021 Hitachi Energy. All rights reserved.
Step
Default
-
Disabled
0.1
10.0
0.1
100.0
0.1
100.0
0.1
0.0
0.1
0.0
-
1 sensor mode
-
Disabled
0.1
10.0
0.1
100.0
0.1
100.0
0.1
0.0
0.1
0.0
-
1 sensor mode
-
Disabled
0.1
10.0
1MRK 511 557-UEN Rev. A
Description
Selection of monitored limits for input 1
Absolute Hysteresis value for input 1
High alarm value limit above which an
upper limit alarm would be issued for
input 1.
High warning value limit above which an
upper limit warning would be issued for
input 1.
Low value limit below which a lower limit
warning would be issued for input 1.
Lower value limit below which a lower
limit alarm would be issued for input 1.
Selection of one or three sensors for
input 1.
Selection of monitored limits for input 2.
Absolute Hysteresis value for input 2
High alarm value limit above which an
upper limit alarm would be issued for
input 2.
High warning value limit above which an
upper limit warning would be issued for
input 2.
Low value limit below which a lower limit
warning would be issued for input 2.
Lower value limit below which a lower
limit alarm would be issued for input 2.
Selection of one or three sensors for
input 2.
Selection of monitored limits for input 3.
Absolute Hysteresis value for input 3
Technical Manual