Signals; Settings; Operation Principle - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
11.5.4

Signals

Table 143: IB16A Input signals
Name
BLOCK
INP
Table 144: IB16A Output signals
Name
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
11.5.5

Settings

The function does not have any parameters available in local HMI or Protection and Control IED
Manager (PCM600)
11.5.6

Operation principle

Integer to boolean 16 conversion function (IB16A) is used to transform an integer (0...65535) into a
set of 16 binary (logical) signals, with the least significant bit mapped to OUT1. IB16A function is
designed for receiving the integer input locally. Activating the BLOCK input will freeze the logical
outputs at the last value.
Technical Manual
Type
Default
Description
BOOLEAN
0
Block of function
INTEGER
0
Integer Input
Type
Description
BOOLEAN
Output 1
BOOLEAN
Output 2
BOOLEAN
Output 3
BOOLEAN
Output 4
BOOLEAN
Output 5
BOOLEAN
Output 6
BOOLEAN
Output 7
BOOLEAN
Output 8
BOOLEAN
Output 9
BOOLEAN
Output 10
BOOLEAN
Output 11
BOOLEAN
Output 12
BOOLEAN
Output 13
BOOLEAN
Output 14
BOOLEAN
Output 15
BOOLEAN
Output 16
© 2021 Hitachi Energy. All rights reserved.
Section 11
Logic
D0E5613T201305151403 v1
D0E5614T201305151403 v1
D0E4794T201305151403 v1
D0E5074T201305151403 v3
141