Precision Binary Inputs - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 15
IED physical connections
Table 403: Inputs for close/open commands and CB drive energy level
Connector
X329
X329
X329
X329
X329
X329
X329
X329
X329
X329
X329
X329
X329
X329
X321
X321
X321
X321
X321
X321
* No separate software designation, as this is the common terminal for the next two signals.
15.2.4

Precision binary inputs

The precision binary inputs are used for accurate detection of status changes of main or auxiliary
contacts in the circuit breaker.
Connectors are delivered with the device. Each connector terminal is connected with one 0.5...2.5
mm² (AWG 20...13) wire or with two 0.5...1.0 mm² (AWG 20...17) wires.
420
Pin
Signal
1
Close in -
2
Close in +
4
Open/Trip in -
5
Open in +
6
Trip in +
8
L1 Spr -
9
L1 Spr OCObk +
10
L1 Spr CObk +
12
L2 Spr -
13
L2 Spr OCObk +
14
L2 Spr CObk +
16
L3 Spr -
17
L3 Spr OCObk +
18
L3 Spr CObk +
13
LED Rst -
14
LED Rst +
15
PBI2 -
16
PBI2 +
17
PBI3-
18
PBI3 +
Binary inputs for spring charge level are intended for circuit breakers in which the
drive energy and the operating capability can differ with the position of the main
storage element (spring). This occurs in spring-hydraulic drives such as Hitachi
Energy models HMB/HMC. The spring charge information is used for compensation
of operating times and for reporting the CB's operating capability. However, if the
breaker is not used for fast reclosing and if the spring is always fully charged prior to
each operation, these inputs need not be connected. Similarly, these inputs are not
used with drives in which the spring is always fully charged by design.
© 2021 Hitachi Energy. All rights reserved.
Description
Close command input from bay control
Open and Trip command inputs from bay
control or protection (common terminal)
Open command input from bay control
Trip command input from protection
L1 spring charge level (common terminal)
L1 spring charge level: OCO blocked
L1 spring charge level: CO blocked
L2 spring charge level (common terminal)
L2 spring charge level: OCO blocked
L2 spring charge level: CO blocked
L3 spring charge level (common terminal)
L3 spring charge level: OCO blocked
L3 spring charge level: CO blocked
Reset latched status LEDs
Spare precision input 2
Spare precision input 3
1MRK 511 557-UEN Rev. A
Software signal
BIO_4.BI1
*
BIO_4.BI2
BIO_4.BI3
*
BIO_4.BI4
BIO_4.BI5
*
BIO_4.BI6
BIO_4.BI7
*
BIO_4.BI8
BIO_4.BI9
PIO_3.PBI1
PIO_3.PBI2
PIO_3.PBI3
GUID-009E5C31-9AAA-4FD9-AA52-603DBD816F8D v1
Technical Manual