Signals - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
12.18.4

Signals

Table 255: ACBMSCBR Input signals
Name
BLOCK
BLOCKFUNC
U3PL
I3PL
REFIN
INPRICLLX
INNOCLLX
INNCCLLX
INPRIOPLX
INNOOPLX
INNCOPLX
TGTANGL1
TGTANGL2
TGTANGL3
CLOSECOMP
OPENCOMP
CANCLCMD
CANOPCMD
CLBLK
OPBLK
CLBYPASS
OPBYPASS
LOADTYPE
LOADGNDG
VREFOK
ALMS1T5A
ALMS6T10A
ALMS1T5B
ALMS6T10B
CLCMDINP
CCLCMDLX
OPCMDINP
Table continues on next page
Technical Manual
Type
Default
Description
BOOLEAN
0
Force all binary outputs to 0
BOOLEAN
0
Block execution of this function and populate outputs with default
values
GROUP
-
Three phase load voltage
SIGNAL
GROUP
-
Three phase load current
SIGNAL
GROUP
-
Three phase preprocessed reference signal
SIGNAL
REAL
0.0
Nominal time from Close command till primary contact closing in
this phase
REAL
0.0
Nominal time from Close command till NO contact closing in this
phase
REAL
0.0
Nominal time from Close command till NC contact opening in this
phase
REAL
0.0
Nominal time from Open command till primary contact opening in
this phase
REAL
0.0
Nominal time from Open command till NO contact opening in this
phase
REAL
0.0
Nominal time from Open command till NC contact closing in this
phase
REAL
0.0
Target switching angle for phase L1
REAL
0.0
Target switching angle for phase L2
REAL
0.0
Target switching angle for phase L3
REAL
0.0
Mechanical compensation offset for closing instant in this phase
REAL
0.0
Mechanical compensation offset for opening instant in this phase
BOOLEAN
0
Closing operation canceled
BOOLEAN
0
Opening operation canceled
BOOLEAN
0
Closing operation blocked
BOOLEAN
0
Opening operation blocked
BOOLEAN
0
Closing operation bypassed
BOOLEAN
0
Opening operation bypassed
INTEGER
1
Type of switched load
INTEGER
0
Type of grounding of switched load
BOOLEAN
0
Source voltage signal is suitable as reference
INTEGER
0
Alarm status integer for input 1 to 5 from MONALMa
INTEGER
0
Alarm status integer for input 6 to 10 from MONALMa
INTEGER
0
Alarm status integer for input 1 to 5 from MONALMb
INTEGER
0
Alarm status integer for input 6 to 10 from MONALMb
BOOLEAN
0
Input close command
BOOLEAN
0
Time stamped controlled closing command for this phase
BOOLEAN
0
Input open command
© 2021 Hitachi Energy. All rights reserved.
Section 12
Monitoring