Hitachi Relion 650 Series Technical Manual page 259

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
Name
Values (Range)
Inp8HystAbsolute
Inp8HiHiLimit
Inp8HiLimit
Inp8LoLimit
Inp8LoLoLimit
Inp8SensorMode
Inp9LimitSelect
Inp9HystAbsolute
Inp9HiHiLimit
Inp9HiLimit
Inp9LoLimit
Inp9LoLoLimit
Inp9SensorMode
BinInp10AlarmMode
BinInp10SensorMode
Technical Manual
Unit
0.0 - 99999.9
-
-99999.9 - 99999.9
-
-99999.9 - 99999.9
-
-99999.9 - 99999.9
-
-99999.9 - 99999.9
-
1 sensor mode
-
3 sensor mode
Disabled
-
Hi, HiHi, Lo, LoLo
Hi, Hi-Hi
Lo, Lo-Lo
Hi, Lo
Hi-Hi, Lo-Lo
Hi
Hi-Hi
Lo
Lo-Lo
0.0 - 99999.9
-
-99999.9 - 99999.9
-
-99999.9 - 99999.9
-
-99999.9 - 99999.9
-
-99999.9 - 99999.9
-
1 sensor mode
-
3 sensor mode
Disable all
-
Enab only Wrn
Enab only Alarm
Enab only Hi Alarm
Enab Wrn & Alarm
Enab Al & Hi Al
Enab Wrn Al &
HiAl
1 sensor mode
-
3 sensor mode
© 2021 Hitachi Energy. All rights reserved.
Step
Default
0.1
10.0
0.1
100.0
0.1
100.0
0.1
0.0
0.1
0.0
-
1 sensor mode
-
Disabled
0.1
10.0
0.1
100.0
0.1
100.0
0.1
0.0
0.1
0.0
-
1 sensor mode
-
Disable all
-
1 sensor mode
Description
Absolute Hysteresis value for input 8
High alarm value limit above which an
upper limit alarm would be issued for
input 8
High warning value limit above which an
upper limit warning would be issued for
input 8.
Low value limit below which a lower limit
warning would be issued for input 8.
Lower value limit below which a lower
limit alarm would be issued for input 8.
Selection of one or three sensors for
input 8.
Selection of monitored limits for input 9
Absolute Hysteresis value for input 9
High alarm value limit above which an
upper limit alarm would be issued for
input 9.
High warning value limit above which an
upper limit warning would be issued for
input 9.
Low value limit below which a lower limit
warning would be issued for input 9.
Lower value limit below which a lower
limit alarm would be issued for input 9.
Selection of one or three sensors for
input 9.
Selection of alarm mode for binary input
10
Selection of one or three sensors for
binary input 10.