Section 5
Local HMI
5.3.3

Signals

Table 10:
Name
CLRLEDS
Table 11:
Name
HMI-ON
RED-S
YELLOW-S
YELLOW-F
CLRPULSE
LEDSCLRD
5.4

Status LEDs

There are three status LEDs on the LHMI, above the LCD screen: Ready (green), Start (yellow), Trip
(red).
The green LED has a fixed function that present the healthy status of the IED. The yellow and red
LEDs are user configured. The yellow LED can be used to indicate that a disturbance report is
triggered (steady) or that the IED is in test mode (flashing). The red LED can be used to indicate a
protection operation command.
The yellow and red status LEDs are configured in the disturbance recorder function, DRPRDRE, by
connecting a start or trip signal from the actual function to a BxRBDR binary input function block in
PCM600 and configuring the SetLEDn setting to Off, Start or Trip for that particular signal.
5.5

Indication LEDs

5.5.1

Identification

Function description
Basic part for LED indication module
Individual LEDs in LHMI alarm groups
5.5.2

Functionality

The function blocks LEDGEN and GRP1_LEDx, GRP2_LEDx and GRP3_LEDx (x=1-15) control, and
supply information about the status of the indication LEDs. Input and output signals of the function
blocks are configured with PCM600. The input signal for each LED is selected individually using SMT
44
LHMICTRL Input signals
Type
Default
BOOLEAN
LHMICTRL Output signals
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
© 2021 Hitachi Energy. All rights reserved.
Description
0
Input to clear the LCD-HMI LEDs
Description
Backlight of the LCD display is active
Red LED on the LCD-HMI is steady
Yellow LED on the LCD-HMI is steady
Yellow LED on the LCD-HMI is flashing
A pulse is provided when the LEDs on the LCD-HMI are cleared
Active when the LEDs on the LCD-HMI are not active
IEC 61850
IEC 60617
identification
identification
LEDGEN
-
GRP1_LED1 -
-
GRP1_LED15
GRP2_LED1 -
GRP2_LED15
GRP3_LED1 -
GRP3_LED15
1MRK 511 557-UEN Rev. A
D0E5952T201305151403 v1
D0E5953T201305151403 v1
D0E5632T201305151403 v2
D0E5721T201305151403 v1
ANSI/IEEE C37.2
device number
-
-
D0E5633T201305151403 v1
Technical Manual