Pulse Timer Function Block Pulstimerqt - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 11
Logic
Function block
INPUT
IEC09000299 V1 EN-US
Figure 62:
Signals
Table 110: INVERTERQT Input signals
Name
INPUT
Table 111: INVERTERQT Output signals
Name
OUT
Settings
The function does not have any parameters available in Local HMI or Protection and Control IED
Manager (PCM600).
11.1.2.4

Pulse timer function block PULSTIMERQT

Identification
Function description
Pulse timer function block
Functionality
Triggered by a positive-going edge (logical 0 to 1 transition) on its input, the output of
PULSETIMERQT is activated (1) for a settable duration. During that time, changes in input value are
ignored.
When the output changes value, the timestamp of the output signal is updated.
The supported "quality" state bits are propagated from the input each execution to the output. A
change of these bits will not lead to an updated timestamp on the output.
Function block
INPUT
IEC09000304 V1 EN-US
Figure 63:
Signals
Table 112: PULSETIMERQT Input signals
Name
INPUT
126
INVERTERQT
OUT
IEC09000299-1-en.vsd
INVERTERQT function block
Type
BOOLEAN
Type
BOOLEAN
PULSETIMERQT
OUT
IEC09000304-1-en.vsd
PULSETIMERQT function block
Type
BOOLEAN
© 2021 Hitachi Energy. All rights reserved.
Default
Description
0
Input signal
Description
Output signal
IEC 61850
IEC 60617
identification
identification
PULSTIMERQT
Default
Description
0
Input signal
1MRK 511 557-UEN Rev. A
GUID-06C5C594-E00B-4FD5-8B0F-4ED05DB348B6 v2
GUID-50A2CEA0-2781-4C5F-B184-F09FC666876F v1
GUID-4D277839-1079-4137-BAEE-A2EF87B518BB v1
ANSI/IEEE C37.2
device number
-
-
GUID-D930E5A7-C564-4464-B97F-C72B4801C917 v2.1.1
GUID-A9E4A2DF-28A9-4082-A36D-964383F38896 v2
PID-1079-INPUTSIGNALS v15
PID-1079-OUTPUTSIGNALS v15
PID-1081-INPUTSIGNALS v15
Technical Manual