Web Server Webserver; Identification; Functionality; Settings - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
The input groups are named INPUT1-x to INPUT8-x and each group supports four analog inputs.
INPUT5-x to INPUT8-x additionally support the diagnostic binary status signals from a merging unit
(see description of MU_4I_4U). If any of INPUT1 through INPUT4 is selected, the diagnostic outputs
assume default value 0.
14.20

Web server WEBSERVER

14.20.1

Identification

Function description
Web server
14.20.2

Functionality

Web server function is used for configuring the access to the IED through the web interface (WHMI)
using a web browser.
14.20.3

Settings

Table 396: WEBSERVER Non group settings (basic)
Name
Values (Range)
Operation
WriteMode
SessionTimeout
HTTPSPortNumber
MaxUsers
Table 397: WEBSERVER Non group settings (advanced)
Name
Values (Range)
Port
14.20.4

Operation principle

For accessing the IED using a web browser, WEBSERVER works as an interface function to accept
requests and send data. The actual webpages to be displayed are defined by HTML files stored in
the IED. WEBSERVER interacts with the authority system in the IED to validate user permissions.
Access to the IED from a web browser can be disabled by setting Operation to "Off".
It is possible to change IED parameters and settings through Web HMI. This feature can be disabled
by setting WriteMode to "Writing disabled".
From a security point of view, it is desirable to terminate a browser session if the user has been idle
for some duration. This duration can be set by SessionTimeout.
Technical Manual
Unit
Off
-
On
Writing disabled
-
Writing enabled
2 - 60
Min
1 - 65535
-
1 - 4
-
Unit
None
-
Front
Rear
All
© 2021 Hitachi Energy. All rights reserved.
IEC 61850
IEC 60617
identification
identification
WEBSERVER
-
Step
Default
-
Off
-
Writing disabled
1
3
1
443
1
2
Step
Default
-
All
Basic IED functions
GUID-93701C18-1852-4054-919D-9EB6A8100FFF v2
GUID-71A1BFD4-58DA-4A12-87FD-614E38E91D7B v1
ANSI/IEEE C37.2
device number
-
GUID-DC133893-7C9D-46AD-828F-7953795F9D72 v1
Description
Operation On/Off
Writing of settings enabled
Session timeout
Port number for https request
Maximum concurrent users
Description
Select network port
GUID-D9F399C0-CD50-4E85-950F-FF4142317132 v1