Step 4 Use two M8x80 stainless steel expansion bolts to secure each of the four legs of
the outdoor unit to the concrete platform or base.
----End

4.5.3.2 Vertical Installation Scenario (NetCol500-A060/NetCol500-A080)

The NetCol500-A080 is used as an example. For details about NetCol500-A060
operations, refer to this section.
Securing an Outdoor Unit to the Ground
Step 1 Secure an outdoor unit to the ground through the four bracket angles by using
M8x80 stainless steel expansion bolts on the side panels, as shown in
Figure 4-42 Securing an outdoor unit to the ground
----End
Securing an Outdoor Unit to the Base
The following takes the two-layer installation of outdoor units as an example. For
the single-layer installation, perform only
Step 1 Secure the first layer of base to the ground using six M12x60 stainless steel
expansion anchor bolts, as shown in
Issue 13 (2023-08-20)
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
Step 1
and
Step
Figure
4-43.
4 Installation
Figure
4-42.
3.
84