Table 3-2 NetCol5000-A optional specifications
Item
Power
system
Power
supply
mode
Pipe
routing
Maximum
current
Condensa
te pump
Water
pump lift
Heating
function
Humidific
ation
function
Humidifie
r water
inlet hose
Reheating
capacity
Issue 13 (2023-08-20)
NetCol
NetCol
5000-
5000-
A050H
A050H
4WD2
40D2
380–415 V AC, 50/60 Hz, 3 Ph+N+PE
Tolerance: –10% to +10% of rated
voltage, rated frequency±3 Hz
Dual power supplies
Top and bottom pipe routing
46 A
Yes
4 m
Yes
No
Yes
No
No
No
6 kW
No
Copyright © Huawei Digital Power Technologies Co., Ltd.
NetCol
NetCol
NetCol
5000-
5000-
5000-
A050H
A050H
A050H
4WE2
40E2
RWE2
440–
480 V
AC, 60
Hz, 3
Ph+PE
Toleran
ce: –
10% to
+10%
of
rated
voltage
, rated
frequen
cy±3
Hz
36 A
Yes
No
Yes
Yes
No
Yes
Yes
No
Yes
6 kW
No
6 kW
3 Technical Specifications
NetCol
NetCol5
5000-
000-
A050H
A050H4
4WE0
0E0
380–415 V AC,
50/60 Hz, 3 Ph+N
+PE
Tolerance: –10%
to +10% of rated
voltage, rated
frequency±3 Hz
Single power
supply
Bottom pipe
routing
46 A
No
-
Yes
No
Yes
No
Yes
No
6 kW
No
34

Advertisement

Table of Contents
loading

Table of Contents