Concrete Platform Requirements
The required concrete platform dimensions are different when the concrete
platform is installed horizontally and vertically. The construction requirements are
as follows:
Concrete Platform Requirements for Horizontal Installation
For details about how to make concrete platforms to horizontally install an
outdoor unit, see
Figure 4-12 Concrete platform dimensions
Table 4-3 Concrete platform dimensions (unit: mm)
Model
NetCol500-
A060
NetCol500-
A080
NetCol500-
A120
Issue 13 (2023-08-20)
The concrete platforms are installed horizontally or with a slope of 5 degrees
at most.
Water can drain away after heavy rainfall.
The strength of the concrete platform must be at least C20.
Figure
4-12.
Block
Width
(W1)
W1 ≥ 250
W1 ≥ 250
W1 ≥ 250
Copyright © Huawei Digital Power Technologies Co., Ltd.
Block
Block
Depth
Height
(D1)
(H)
D1 ≥ 250
150–250
D1 ≥ 250
150–250
D1 ≥ 250
150–250
4 Installation
Center
Center
Distance
Distance
(W2)
(D2)
924
1047
924
1877
2018
1047
52