Installation Requirements For The Water-Cooled Module - Huawei NetCol5000-A050 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Figure 4-17 Dimensions of the concrete platform for horizontally installing low
temperature components
Table 4-7 Dimensions of the concrete platform for low temperature components
(unit: mm)
Block Width
(W)
W ≥ 600

4.1.5 Installation Requirements for the Water-Cooled Module

Issue 13 (2023-08-20)
Block Depth
(D)
D ≥ 400
Installation environment: Enclosed indoor environment in which the
temperature and humidity can be controlled within the ranges of 4°C to 45°C
and 5% RH to 90% RH respectively. If the indoor installation position is
ventilated, it should be more than 3.7 km away from the sea or pollution
sources (such as salt lakes, chemical plants, mineral plants, thermal power
plants, and coal mines).
Take antifreezing measures for cooling water pipes if the water-cooled
module is installed in low temperature environments (4°C). To prevent
ethylene glycol solution from corroding pipes, corrosion inhibitor should be
mixed into the glycol solution. For details about the mixing scheme, consult
the ethylene glycol vendor.
Wrap thermal insulation layers for pipes connecting the water-cooled module.
The upstream supply water pressure for the water-cooled module shall be
greater than or equal to 0.35 MPa.
The water quality of the water-cooled module shall meet the following
requirements.
Check Item
Unit
pH (25°C)
-
Turbidity
NTU
Copyright © Huawei Digital Power Technologies Co., Ltd.
Block Height
W1
(H)
150–250
223
Makeup Water
7.5–9.5
≤ 5
4 Installation
D1
130
Circulating
Water
7.5–10
≤ 10
56