Figure 12-18 Deleting historical alarms
Step 2 Tap Confirm to delete all historical alarms.
----End

12.3.11 How Do I Clear Component Runtime?

Context
Performance value clearance can be performed only after component
maintenance. Otherwise the component may run overtime and degrade
performance.
Procedure
Step 1 On the home screen, choose Maint > Performance Maint.
Step 2 Tap Clear of a specific performance parameter to clear its runtime.
----End

12.3.12 How to Calibrate a Sensor

Context
Calibrate a sensor if the displayed temperature or humidity on the sensor deviates
from the actual value. For example, if the return air temperature measured by
other temperature detection devices at the return air detection point is 20°C while
the value measured by the sensor is 22°C, the sensor has an error of 2°C, and the
calibration value should be set to –2°C.