Issue 13 (2023-08-20)
Check Item
Unit
Conductivity
μS/cm
(25°C)
mg/L
-
Cl
Total Fe
mg/L
Calcium
mg/L
hardness (in
CaCO
)
3
Total alkalinity
mg/L
(in CaCO
)
3
Dissolved oxygen
mg/L
Organic
mg/L
phosphorus (in
P)
NO TE
For detailed requirements, see GB/T 29044.
A maximum of four water-cooled modules can be stacked, as shown in the
following figure.
Figure 4-18 Stacking scenario
(1) Water strainer
Copyright © Huawei Digital Power Technologies Co., Ltd.
Makeup Water
Circulating
Water
≤ 600
≤ 2000
≤ 250
≤ 250
≤ 0.3
≤ 1.0
≤ 300
≤ 300
≤ 200
≤ 500
-
≤ 0.1
-
≤ 0.5
4 Installation
57