NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Figure 4-88 Teamwork communications cable and FE monitoring communications
cable
(1) Orange-white
(5) Blue-white
Figure 4-89 RS485 monitoring communications cable
(4) Blue
----End
4.9.8.2 Smart Module Networking Scenario
Step 1 Connect teamwork and monitoring communications cables.
Networking
Protocol
Issue 13 (2023-08-20)
(2) Orange
(6) Green
NO TE
Crimp only the core wire 4 (blue) and core wires 5 (blue-white) on the RJ45 connector of
the RS485 monitoring communications cable. Do not crimp core wires 1, 2, 3, 6, 7, and 8.
Otherwise, communication interference may occur.
NO TE
Smart module networking is the networking of in-row smart cooling products using the
ECC800 in a smart module.
Teamwork
MAC_CAN
Copyright © Huawei Digital Power Technologies Co., Ltd.
(3) Green-white
(4) Blue
(7) Brown-white
(8) Brown
(5) Blue-white
Monitoring
Modbus-TCP
4 Installation
124