Huawei NetCol5000-A050 User Manual page 65

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Figure 4-14 Concrete platform dimensions
Table 4-5 Concrete platform dimensions (unit: mm)
Model
NetCol500-A060
(Class B)
NetCol500-A060
(Class C)
NetCol500-A080
NetCol500-A120
a: A base is required for securing. For details about securing during vertical
installation, see
Figure 4-15
installation.
Issue 13 (2023-08-20)
Block Width
(W1)
W1 ≥ 250
W1 ≥ 250
W1 ≥ 250
W1 ≥ 250
a
4.5.3.3 Vertical Installation Scenario
and
Figure 4-16
Copyright © Huawei Digital Power Technologies Co., Ltd.
Block
Depth (D)
D ≥ 500
D ≥ 500
D ≥ 500
D ≥ 500
show the mounting hole for outdoor unit vertical
4 Installation
Block
Center
Height (H)
Distance
(W2)
150–250
1036.5
150–250
977
150–250
1744.5
150–250
2011
(NetCol500-A120).
54