NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Tab
Issue 13 (2023-08-20)
Parameter
Humidifying function
Dehumidifying
function
DO_1
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Power-On Commissioning
Description
● Enable: The device starts humidifying
when the ambient humidity is lower
than the humidity setpoint.
● Enabled when active power supply is
working: The device starts
humidifying only when the active
power supply is used and the
ambient humidity is lower than the
humidity setpoint by a certain range.
● Disable: The humidifying function is
disabled.
● Enable: The device starts
dehumidifying when the ambient
humidity is higher than the humidity
setpoint.
● Disable: The dehumidifying function
is disabled.
● If this parameter is set to Smoke &
Water only, DO_1 acts according to
DO_1 action when a smoke or water
overflow alarm is generated.
● If this parameter is set to Critical
alarm, DO_1 acts according to DO_1
action when a critical alarm is
generated.
● If this parameter is set to Major
alarm, DO_1 acts according to DO_1
action when a major alarm is
generated.
● If this parameter is set to Alarm,
DO_1 acts according to DO_1 action
when a critical alarm, major alarm,
or warning is generated.
● If this parameter is set to Startup
status, DO_1 acts according to DO_1
action when the unit is started.
● If this parameter is set to No, no
alarm is generated when DO_1 is
disconnected.