NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Parameter
Enable teamwork
CAN resistor
Teamwork function
Networking mode
Teamwork parameter
synchronization
Number of systems in
this group
Number of running
systems in this group
Issue 13 (2023-08-20)
Description
If CAN network is selected, set Enable teamwork
CAN resistor to Yes for the first and last units. If
Enable teamwork CAN resistor is set to No for the
first and last units, the CAN communication quality will
be affected, and even the teamwork CAN networking
will fail.
Yes: The teamwork control CAN resistor is enabled for
the unit.
No: The teamwork control CAN resistor is disabled for
the unit.
Specifies whether to enable the teamwork function. Set
this parameter based on onsite heat load distribution.
● Disable: A unit operates independently.
● Enable: A unit operates in team with other units.
Specifies the networking mode for teamwork control.
The networking mode selected on the screen must
match the actual networking mode. Otherwise, the
teamwork function is unavailable.
If Teamwork function and Teamwork parameter
synchronization are both set to Enable, you can select
Set Local or Set Teamwork when setting parameters.
NOTE
Specifies the total number of units in this group. The
value is an integer ranging from 1 to 32.
NOTE
Specifies the number of running units in this group. The
value is an integer ranging from 1 to the value of
Number of systems in this group.
NOTE
Copyright © Huawei Digital Power Technologies Co., Ltd.
● Set Local: Set parameters for the local unit.
● Set Teamwork: Set parameters for all units in a teamwork
group.
This parameter is displayed after Teamwork function is set to
Enable.
This parameter is displayed after Teamwork function is set to
Enable.
6 Power-On Commissioning