NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Figure 11-34 Installing a liquid level detector
Step 7 Install the water pan cover, and close the front door.
Step 8 Power on the device and tap Start on the home screen. Ensure that the smart
cooling product is running normally without any alarms.
----End
11.11 Replacing a Condensate Pump
Prerequisites
●
●
●
Before removing the condensate pump, drain water from the water pan
completely.
Context
The condensate pump needs to be maintained from the front door.
Issue 13 (2023-08-20)
A condensate pump needs to be replaced.
A spare condensate pump of the same model is available and functional.
Tools: flat-head insulated torque screwdriver, Phillips insulated torque
screwdriver, insulated torque socket wrench
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
11 Parts Replacement
227