Huawei NetCol5000-A050 User Manual page 155

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Figure 6-6 Quick settings
Tab
Select
Language
Date and
Time
Settings
Teamwork
Settings
Issue 13 (2023-08-20)
Parameter
Language
Date format
Date settings
Time zone
Time
Teamwork group num
System address
Teamwork function
Networking mode
Number of systems in
this group
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Power-On Commissioning
Description
Specifies the display language.
Specifies the date format.
Specifies the date.
Specifies the time zone.
Specifies the time.
Specifies the planned teamwork group
number. This parameter should be the
same for all units in the same teamwork
group.
Specifies the planned unit address. The
addresses of units in the same
teamwork group must be unique.
Specifies whether to enable the
teamwork function. Set this parameter
based on onsite heat load distribution.
● Disable: A unit operates
independently.
● Enable: A unit operates in team with
other units.
Specifies the networking mode for
teamwork control. The networking
mode selected on the screen must
match the actual networking mode.
Otherwise, the teamwork function is
unavailable.
Specifies the total number of units in
this group. The value is an integer
ranging from 1 to 32.
NOTE
This parameter is displayed after Teamwork
function is set to Enable.
144