Huawei NetCol5000-A050 User Manual page 151

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Figure 6-3 Precharging refrigerant when no low temperature component is
configured
(1) Refrigerant cylinder
(4) Connection nut
Figure 6-4 Precharging refrigerant when a low temperature component is
configured
(1) Refrigerant cylinder (2) Electronic scale
(5) Connection nut
Step 2 Slightly open the refrigerant cylinder valve and loosen the connection nut of the
pressure gauge. Tighten the nut when cold air escapes out of the nut.
Step 3 Put the refrigerant cylinder upside down on the electronic scale. Clear the reading
on the balance.
Issue 13 (2023-08-20)
(6) Low-pressure
needle valve
Copyright © Huawei Digital Power Technologies Co., Ltd.
(2) Electronic scale
(5) Low-pressure needle valve (6) Discharge pipe needle
(3) Pressure gauge 1
(7) Discharge pipe
needle valve
6 Power-On Commissioning
(3) Pressure gauge
valve
(4) Pressure gauge 2
(8) Liquid pipe needle
valve
140

Advertisement

Table of Contents
loading

Table of Contents