Huawei NetCol5000-A050 User Manual page 115

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
To install a low temperature component horizontally, you are recommended to
place the low temperature component on one side of the outdoor unit.
4-66
inverted trap respectively at the inlet and outlet pipe ports on the outdoor unit
condenser, preventing refrigerant from returning.
Figure 4-66 Ports on the low temperature component
(1) Connecting to the indoor unit liquid pipe:
5/8 inch (15.88 mm)
(3) Connecting to the outdoor unit gas pipe:
7/8 inch (22.22 mm)
Figure 4-67 Connecting the outdoor unit
(1) Connecting to the indoor unit liquid pipe
(3) Connecting to the outdoor unit gas pipe
Issue 13 (2023-08-20)
and
Figure 4-67
show the related inlet and outlet pipe ports. Install an
Copyright © Huawei Digital Power Technologies Co., Ltd.
(2) Connecting to the outdoor unit liquid pipe:
5/8 inch (15.88 mm)
(4) Connecting to the indoor unit gas pipe: 7/8
inch (22.22 mm)
(2) Connecting to the indoor unit gas pipe
(4) Connecting to the outdoor unit liquid pipe
4 Installation
Figure
104