NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Tab
Comm
Settings
----End
Follow-up Procedure
After powering on, the compressor starts preheating, and the system generates an
alarm indicating that the compressor is preheating (for 12 hours). Do not start the
smart cooling product before the preheating ends.
Start.
Figure 6-7 Compressor preheating warning
If you need to query the remaining preheating time, choose Running > Device
Details > Compressor on the home screen.
Issue 13 (2023-08-20)
Parameter
Humidity setpoint
Modbus Comm
address
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Power-On Commissioning
Description
After the temperature and humidity
control type and the humidity value
under this type are set, the device
performs regulation based on the
settings.
40%–60% is recommended.
Enter the communication address
planned for the smart cooling product.
The management system communicates
with the smart cooling product through
this address. The communication
addresses of the two smart cooling
products connected to the same
management system must be different.