Figure 3-2 NetCol500-W dimensions
Figure 3-3 NetCol500-W hole dimensions
Table 3-5 Operating environment specifications of the water-cooled module
Item
Power system
Refrigerant
Heat exchanging
capacity
Temperature range
Humidity range
Storage
temperature
Storage humidity
Inlet water
temperature range
of chilled water
Issue 13 (2023-08-20)
NO TE
● If an outdoor unit needs to be used at a site 3.7–10 km away from the coast in a class B
environment, it is recommended that the unit be installed in a shielded area, such as a
podium building, ground, or building rear, to prevent mechanical parts from being
corroded by sea wind (the functionality and reliability of the system must not be
affected). Alternatively, use an outdoor unit that supports class C environments to avoid
corrosion. If the site is more than 10 km away from the coast, the unit can be properly
installed.
● The NetCol500-A060MS1E0 outdoor unit must not be installed in class D environments,
and other outdoor units must not be installed in class C or class D environments.
Technical Specifications
220–240 V AC, 1 Ph+N+PE, 50/60 Hz
R410A
55 kW
4°C to 45°C
5%–90% RH
–40°C to +70°C
5%–95% RH (non-condensing)
10°C to 37°C