Advertisement

5.5. Preparing the installation site

To ensure proper alignment and installation of the drive, prepare the floor as follows:
The floor must be able to support the weight of the drive (minimum 1500 kg/m
The overall incline of the floor across 5 m must not exceed 5 mm.
1 mm
1 mm
Key:
(1)
Tolerance from mean ground ± 1 mm
(2)
Surface or floor
(3)
Tolerance for incline: 5 mm incline on 5 m length

Fig. 34. Floor inclination

The floor must be even.
Check the evenness and incline of the floor well in advance so that work for improving the
surface is completed before the installation of the drive.
Use a spirit level or flooring rule with a vial for checking.
Recommended length: 1 to 2 m.
If the surface cannot be improved, place shims or leveling plates under the base frame at
appropriate distances (every 1 m) for adjustment.
Leveling plates of the following size are recommended: 100 mm × 100 mm
Drill the fixing holes before moving the drive to the final location.