Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

3. Check that no alarm or fault messages are displayed on the CDP control panel.
When a fault message is displayed on the CDP control panel, reset the fault.
If a fault cannot be reset, it must be rectified by the responsible personnel.
When no alarms and faults are present and the drive is ready, the CDP control panel displays
ReadyOn.
1 L ->
0.0 rpm
StateINU
ReadyOn
MOTOR SP
0.00 rpm
POWER
0.0 kW
4. Press the SUPPLY ON push button on the control compartment door to charge the DC link.
The push button flashes during charging.
The status line of the CDP control panel alternates between Charging and AuxiliaryOn.
1 L ->
0.0 rpm
StateINU
Charging
MOTOR SP
0.00 rpm
POWER
0.0 kW
After charging has been finished, the following takes place:
The main circuit breaker closes automatically.
The SUPPLY ON push button lights up permanently.
1 L ->
0.0 rpm
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
5. Enter the reference value.
For more information, see Section 9.3.2, "Entering a reference value", page 157.
1 L ->
[600.0 rpm] 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
PRODUCT
ACS5000W gen. 2
Alternating display message:
Charging
AuxiliaryOn
0
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS799208 E01
OPERATION
REV.
LANG.
PAGE
J
en
131/186