Checking Wire And Cable Connections; Checking And Replacing Filter Mats; Table 12 Filter Mat Specifications - ABB ACS5000 User Manual

Water-cooled (generation 2)
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

10.6.8. Checking wire and cable connections

NOTICE
Risk of component damage. Vibration can loosen electrical connections and cause equipment
failure. Excessive force damages the capacitor bushings.
→ Tighten to the torque value on the label attached to the capacitor; DO NOT exceed 20 Nm if
the tightening torque value is not specified.
→ Check all power and control cable connections and tighten them if necessary.
→ Check that all plugs and connectors are tight.

10.6.9. Checking and replacing filter mats

Inspection intervals
Service during operation
Filter mat class
Location

TABLE 12 Filter mat specifications

Location
IP class
WCU
IP 54
(back wall)
EXU
IP 54
PCU
IP 42
PCU
IP 42
(FS2/FS4 only)
PRODUCT
ACS5000W gen. 2
See the "ACS5000 preventive maintenance schedule", 3BHS855274 E01.
Possible
G3 (EN779)
In IP 54 rated drives, the filter mats are behind the ventilation grids of
the roof-mounted cooling units on COU and WCU cabinets. In IP 42-
rated drives, the filter mats are behind the ventilation grids in the PCU
and WCU cabinet doors.
Width
Filter class
(mm)
G3 T15/150
250
G3 T15/150
745
G3 T15/150
600
G3 T15/150
600
DOCUMENT KIND
User manual
PREVENTIVE AND CORRECTIVE MAINTENANCE
Height
Depth
(mm)
(mm)
125
10
375
10
652
10
352
10
DOCUMENT ID.
3BHS799208 E01
ABB ID
3BHB028115R0002
3BHB028115R0004
3BHB030369R0800
3BHB030369R0500
REV.
LANG.
PAGE
J
en
177/186