9.2.5.3. Enabling the local lock

To enable the local lock, set parameter 16.04 to 2 (LOCKED).
With this parameter setting, local control (including the LOC-REM key) is disabled.
If the CDP control panel or a DriveWindow PC is in local control mode at the time that the
local lock is enabled, they remain in local control mode until they are switched to remote
control mode. This means that the CDP control panel displays the letter L until you press the
LOC-REM key.
9.2.5.3.1. Disabling the local lock
To disable the local lock, set parameter 16.04 to 1 (OPEN).
With this parameter setting, switching between remote and local control is enabled.

9.2.5.4. Remote control

In remote control mode, operational commands or reference values usually come from a higher-
level control system via fieldbus or remote I/O.
However, with the following parameter settings it is possible to start and stop the drive, to set
the direction of rotation, and to enter reference values from the CDP control panel.
11.01 EXT1 START/STOP/DIR = 10 (KEYPAD) or
12.03 EXT REF1 SELECT = 1 (KEYPAD) and
12.02 EXT1/EXT2 SELECT = 1 (EXT1)
11.02 EXT2 START/STOP/DIR 10 (KEYPAD) or
12.06 EXT REF2 SELECT = 1 (KEYPAD) and
12.02 EXT1/EXT2 SELECT = 2 (EXT2)
To enter the remote control mode, press the LOC-REM key.
A blank space indicates full remote control from a higher-level control system.
R
The letter
indicates partial remote control (some commands are enabled locally).
1 R
600.0 rpm 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
PRODUCT
ACS5000W gen. 2
1 L ->
600.0 rpm 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS799208 E01
CDP CONTROL PANEL
REV.
LANG.
PAGE
J
en
156/186