6.4.3. Grounding the drive and the motor (multi-point bonding)

Multi-point bonding is the preferred method for voltage source converter applications.
NOTE – Multi-point bonding is not allowed for high-speed applications; use single-point
bonding instead (see Section 6.4.4, "Grounding the drive and the motor (single-point bonding)",
page 89).
For more information, see "Power cables engineering guideline", 3BHS542290 E01.
Fig. 53 shows the multi-point connections for grounding a drive and a motor in the
COU compartment.
AC5000W
PCUs
COU
1L1
1L2
1
2
3
2
2
3
Motor
3
2
2
1
2
3
U
V

Fig. 53. Grounding the drive and the motor (multi-point bonding)

PRODUCT
ACS5000W gen. 2
1L3
1
1
2
3
5
3
4
3
5
1
2
3
1
W
M
DOCUMENT KIND
User manual
6
Key:
(1)
PE busbar
(2)
Cable screen
(3)
Cable shield/armor
(4)
Equipotential bonding conductor
(optional)
(5)
Ground conductor
(6)
System ground (grounding network of
installation site)
6
DOCUMENT ID.
3BHS799208 E01