Local And Remote Control Mode; Local Control; Disabling / Enabling Local Lock Function - ABB ACS5000 User Manual

Water-cooled (generation 2)
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

6. To cancel the setting and keep the original setting, press any of the mode selection keys.
The selected keypad mode is entered.
ACT
PAR
FUNC
DRIVE

9.2.5. Local and remote control mode

The local-remote feature of the CDP control panel allows selecting the control location of the
drive. Possible are:
Local control (L)
Remote control (R)
NOTE – In this context, remote control is not necessarily equivalent to higher-level control.
For more information, see Section 9.2.5.4, "Remote control", page 156.

9.2.5.1. Local control

In local control mode, full operational control of the drive is enabled from the local operator
panel. Commands from remote have no effect.
To enter the local control mode, press the LOC-REM key.
Local control is indicated by the letter L.

9.2.5.2. Disabling / enabling local lock function

Accidental switching from remote control to local control can be prevented with the local lock
function.
The corresponding parameter is 16.04 LOCAL LOCK and belongs to the parameter group
16 SYSTEM CTRL INPUTS .
PRODUCT
ACS5000W gen. 2
1 L ->
0.0 rpm
UPLOAD
<= <=
DOWNLOAD => =>
CONTRAST
6
1 L ->
600.0 rpm 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS799208 E01
CDP CONTROL PANEL
REV.
LANG.
PAGE
J
en
155/186

Advertisement

Table of Contents
loading