6.8.2.2. Connecting cables in COU
6.8.2.2.1. Shielded cables
–
If you use twisted pair cables, leave the unshielded cable ends twisted until they reach
the terminals.
–
Leave unshielded conductor ends as short as possible.
–
Use a shield grounding clamp (Fig. 75) to fasten the overall shield and the individual shields
to the ground busbar (8, Fig. 75).
Fig. 75. Shield grounding clamp
1
2
3
Fig. 76. COU customer interface section