6.7.2. Connecting the cables
CAUTION
Risk of flashover! High voltages in the terminal unit can cause flashover between the
electric potential of different conductors and the electric potential of a conductor and
earth. When you route and connect the cables, maintain the following
minimum clearances:
→ 70 mm between cable lugs of conductors with a different potential
→ 70 mm between the cable lug of a conductor and the parts with earth potential
→ 30 mm between cables with a different potential
6.7.2.1. Checking the cable insulation
–
Measure the insulation of each cable before connection and verify that the results are within
the specification of the cable manufacturer.
–
Leave the conductors unconnected at both ends until the commissioning personnel has
given permission to connect them.
6.7.2.2. Connecting the cables
Connect the cables to their corresponding busbars:
–
Transformer cables to the busbars inside the primary PCU (Fig. 67)
–
Motor cables to the busbars inside the COU (Fig. 69)
–
Ground cable to the PE ground busbar