Stop Sequence Of The Drive; Emergency-Off Sequence - ABB ACS5000 User Manual

Water-cooled (generation 2)
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

8.7.2. Stop sequence of the drive

1) Operation
2) ReadyRef
3) Stop command
4) Stopping
Speed ramps down
Inverter stops modulating
5) ReadyRun
6) Off command
MCB opens
DC link discharges
Cooling system switches off after a delay
7) ReadyOn
Ground drive
PCU doors are released for opening
Switch off auxiliary power supply
8) NotReadyOn

8.7.3. Emergency-off sequence

1) Operation
2) ReadyRef
3) Emergency-off command
MCB opens
Inverter stop modulating
Speed coasts down
4) NotReadyOn