Mitsubishi Electric MELSEC iQ-R Series User Manual page 294

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Master station  remote station
When data is transmitted from the master station (RY/RWw) to a remote station (output).
Calculation value
Normal value
Maximum value
■Variable
Name of variable
SM
LS
Rio
n2
Master station  local station
When data is transmitted from a local station to the master station as follows:
• Master station (RX)  local station (RY)
• Master station (RWr)  local station (RWw)
• Master station (LB)  local station (LB)
• Master station (LW)  local station (LW)
Calculation value
Normal value
Maximum value
■Variable
Name of variable
SM
LS
SL
n1
Master station  local station
When data is transmitted from the master station to a local station as follows:
• Master station (RY)  local station (RX)
• Master station (RWw)  local station (RWr)
• Master station (LB)  local station (LB)
• Master station (LW)  local station (LW)
Calculation value
Normal value
Maximum value
■Variable
Name of variable
SM
LS
SL
n3
APPX
292
Appendix 7 Processing Time
Station-based block data assurance
(SM  n2) + (LS  1) + Rio
(SM  n2) + (LS  2) + Rio
Description
Master station sequence scan time
Communication cycle intervals (can be checked in the SW0060)
Processing time of the remote station
Round up the calculated value to the nearest integer of (LS  SM)
Station-based block data assurance
If LS < SL: (SM  1) + (LS  (n1 + 1)) + (SL  1)
If LS  SL: (SM  1) + (LS  (n1 + 2))
(SM  2) + (LS  (n1 + 2)) + (SL  1)
Description
Master station sequence scan time
Communication cycle intervals (can be checked in the SW0060)
Local station sequence scan time
Round up the calculated value to the nearest integer of (SM  LS)
Station-based block data assurance
If LS < SM: (SM  1) + (LS  (n3 + 1)) + (SL  1)
If LS  SM: (LS  (n3 + 2)) + (SL  1)
(SM  1) + (LS  (n3 + 2)) + (SL  2)
Description
Master station sequence scan time
Communication cycle intervals (can be checked in the SW0060)
Local station sequence scan time
Round up the calculated value to the nearest integer of (SL  LS)
No station-based block data assurance
(SM  1) + (LS  1) + Rio
(SM  2) + (LS  2) + Rio
Unit
s
s
s
No station-based block data assurance
(SM  1) + (LS  2) + (SL  1)
(SM  2) + (LS  3) + (SL  1)
Unit
s
s
s
No station-based block data assurance
(SM  1) + (LS  2) + (SL  1)
(SM  1) + (LS  3) + (SL  2)
Unit
s
s
s