No.
Name
Description
SW0076
PORT1 total
Stores the cumulative count that data was received at the P1 side.
number of
When 'Clear communication error count' (SB0006) is turned on, the stored count
received data
is cleared.
(lower 1 word)
When FFFFFFFFH (maximum value 4294967295) is counted, counting stops.
SW0077
PORT1 total
number of
received data
(upper 1 word)
SW0078
Transient
Stores the transient transmission time that are calculated by the number of slave
transmission
stations and the number of link device points set in "Network Configuration
Settings" of "Basic Settings". (Unit: s)
time (calculation
value)
SW0079
Watchdog
Stores the processing time required for the watchdog counter to monitor cyclic
counter
communications. The processing time is calculated according to the settings of
the slave station actually connected. (Unit: s)
processing time
(calculation
value)
SW007A
Transient
Stores the additional time required for "Communication Period Interval Setting"
transmission
and "Transient Transmission Time" of "Communication Period Setting" under
"Basic Settings". (Unit: s)
additional time
(calculation
value)
SW007C
PORT2 cable
Stores the cumulative count that was detected for cable disconnections at the P2
disconnection
side.
detection count
When 'Clear communication error count' (SB0006) is turned on, the stored count
is cleared.
When FFFFH (maximum value 65535) is counted, the value returns to 0 and the
module continues to count.
SW007D
PORT2 receive
Stores the cumulative count that error data was received at the P2 side.
error detection
The count stores only error data that is not transmitted to all stations.
count
When 'Clear communication error count' (SB0006) is turned on, the stored count
is cleared.
When FFFFH (maximum value 65535) is counted, counting stops.
SW007E
PORT2 total
Stores the cumulative count that data was received at the P2 side.
number of
When 'Clear communication error count' (SB0006) is turned on, the stored count
received data
is cleared.
(lower 1 word)
When FFFFFFFFH (maximum value 4294967295) is counted, counting stops.
SW007F
PORT2 total
number of
received data
(upper 1 word)
SW0080 to
REMFR/REMTO
Stores the execution status of the REMFR/REMTO/REMFRD/REMTOD
SW009F
instruction
instruction for each channel.
execution status
SW0080 to SW009F: Channel 1 to Channel 32
0: Completed successfully
1 or greater: Completed with an error (Error code is stored.)
Availability
Master
Local station
station
Unicast
mode
Appendix 5 List of Link Special Register (SW)