Error
Error definition and causes
code
360DH
• When multiple network modules are set as
the target modules for inter-module
synchronization, the network module with
the firmware version that cannot be set as
the inter-module synchronous master.
• An error has been detected in the inter-
module synchronization function.
3C00H
A hardware failure has been detected.
3C01H
A hardware failure has been detected.
3C02H
A hardware failure has been detected.
3C0FH
A hardware failure has been detected.
3C10H
A hardware failure has been detected.
3C13H
A hardware failure has been detected.
3C14H
A hardware failure has been detected.
3C2FH
An error was detected in the memory.
3E01H
Network type of the own station is
unexpected setting.
3E02H
A time synchronization error was detected.
3E03H
An error was detected in the memory.
3E04H
A hardware failure has been detected.
3E07H
A hardware failure has been detected.
4000H to
Errors detected by the CPU module ( MELSEC iQ-R CPU Module User's Manual (Application))
4FFFH
C011H
The port number of the external device is not
set correctly.
4 TROUBLESHOOTING
214
4.5 List of Error Codes
Action
• Update the firmware version of the network module which is set for the
inter-module synchronous master to "11" or later.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module or base unit. Please consult your local Mitsubishi
representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module, base unit, or extension cable. Please consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module, base unit, or extension cable. Please consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module, base unit, or extension cable. Please consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module, base unit, or extension cable. Please consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module, base unit, or extension cable. Please consult your local
Mitsubishi representative.
Reset the CPU module, and run it again. If the same error occurs again
even after doing so, the possible cause is a hardware failure of the error
module or CPU module. Please consult your local Mitsubishi representative.
Reset the CPU module, and run it again. If the same error occurs again
even after doing so, the possible cause is a hardware failure of the error
module or CPU module. Please consult your local Mitsubishi representative.
Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of the
error module. Please consult your local Mitsubishi representative.
Rewrite the module parameter using the engineering tool. If the same error
occurs again even after taking the above, the possible cause is a hardware
failure of the error module. Please consult your local Mitsubishi
representative.
Reset the CPU module, and run it again. If the same error occurs again
even after doing so, the possible cause is a hardware failure of the error
module or CPU module. Please consult your local Mitsubishi representative.
Reset the CPU module, and run it again. If the same error occurs again
even after doing so, the possible cause is a hardware failure of the error
module or CPU module. Please consult your local Mitsubishi representative.
Reset the CPU module, and run it again. If the same error occurs again
even after doing so, the possible cause is a hardware failure of the error
module or CPU module. Please consult your local Mitsubishi representative.
Reset the CPU module, and run it again. If the same error occurs again
even after doing so, the possible cause is a hardware failure of the error
module or CPU module. Please consult your local Mitsubishi representative.
Correct the port number of the external device.