Refresh Settings

Assign link refresh ranges between the devices described below.
• SB, SW of the RJ71GN11-T2  Module label of the CPU module
• SB, SW, link devices (RX, RY, RWr, RWw, LB, LW) of the RJ71GN11-T2  Devices of the CPU module
Setting method
The procedure for the refresh settings is shown below.
1.
Set the required items.
2.
Click the [Apply] button to finish the refresh settings.
Setting items
Item
Description
Device Assignment
Right-click in the setting window and select a link device assignment
Method
method from the "Device Assignment Method" menu.
• Start/End: Enter the start and end numbers of link devices.
• Points/Start: Enter the numbers of points and start numbers of link
devices.
Link Side
Set the link refresh ranges of the link special relay (SB) and link special
register (SW). One range can be set for each SB and SW. ( Page 29
Link refresh)
Ex.
00000H
·
001FFH
00000H
·
001FFH
CPU Side
RJ71GN11-T2
(1) Module label
(1)
SB
00000H
SW
SW
001FFH
RCPU
Setting range
• Start/End
• Points/Start
(Default: Start/End)
■Device Name
• SB (fixed)
• SW (fixed)
■Points
• SB: 16 to 4096
• SW: 1 to 4096
(Default: 4096)
■Start
• SB: 0H to FF0H (set in increments of 16 points)
• SW: 0H to FFFH (set in increments of 1 point)
(Default: 00000H)
■End
·
• SB: FH to FFFH (set in increments of 16 points)
• SW: 0H to FFFH (set in increments of 1 point)
(Default: 00FFFH)
■Target
• Module Label
• Specify Device
(Default: Module Label)
■Device Name
• Module Label: 
• Specify Device (link side is SB): SB, M, L, B, D, R, ZR,
RD
• Specify Device (link side is SW): SW, M, L, B, D, R, ZR,
RD
(Default: Grayout)
■Points, End
• Module Label: 
• Specify Device: Displayed according to setting of
"Start".
(Default: Grayout)
■Start
• Module Label: 
• Specify Device: Device range of CPU modules (Set bit
devices in increments of 16 points and word devices in
increments of 4 points.)
(Default: Grayout)