Mitsubishi Electric MELSEC iQ-R Series User Manual page 121

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Simple
Detailed
Description
display
display
Number
RWw
Assign RWw/RWr points in increments of 4. ( Page 19 Communications using
of input/
Setting
RX, RY, RWr, and RWw)
output
Modules with settings provided by the profile are automatically set from selected
RWr Setting
word
models. (Excluding modules with a number of points that is not fixed)
*4
points
LB Setting
Assign LB points in increments of 16 and LW points in increments of 1. ( Page
24 Communications using LB and LW)
Modules with settings provided by the profile are automatically set from selected
models. (Excluding modules with a number of points that is not fixed)
LW Setting
Parameter Automatic
Set whether to set the parameters of each slave station automatically.
Setting
This cannot be set for extension modules. However, the parameter automatic
setting of extension modules is interlocked with the settings of the connected main
module.
PDO Mapping Setting
Set the PDO mapping to the station that supports CANopen communications.
( Page 127 PDO mapping setting)
IP Address
Set the IP address of a station that performs cyclic transmission.
Subnet Mask
Set a subnet mask to identify a network address.
Set the same value for the master station and slave station. Even if a slave station
has a different subnet mask from the master station, it does not result in an input
error.
If 255.255.255.255 is set, leave it empty.
Default Gateway
Set the default gateway address to connect to the external network.
If 223.255.255.255 is set, leave it empty.
Reserved/Error Invalid
Set the slave station as a reserved station or error invalid station.
Station
• No Setting: The slave station is connected to the network.
• Reserved Station: The slave station is reserved for future expansion. By using a
reserved station, link device assignment will not change even if the slave station
is added (reservation is canceled). Therefore, modification of the program is not
required. Physical connection of the slave station on the network is not required.
• Error Invalid Station: Even if a slave station is disconnected during data link, the
master station will not detect the slave station as a faulty station.
Network Synchronous
Set whether to synchronize each slave station with network synchronous
*2
Communication
communication.
Communication Period
When multiple communication cycles are set, set the cycle of each slave station.
Setting
( Page 42 Communication cycles coexistence)
Station Information
■Alias
Enter the name of a device if required.
The name entered is displayed in "Network Status" of the "CC-Link IE TSN/CC-
Link IE Field Diagnostics" window.
For the extension module of the remote station, the name is not displayed in the
"CC-Link IE TSN/CC-Link IE Field Diagnostics" window, even if entered.
■Comment
Information entered in "Comment1" on the "Properties" window displayed by right-
clicking the module in the list of stations or the network map is displayed.
■Station-specific mode setting
Set the station-specific mode of the slave station. (Only when the slave station
supports the station-specific mode)
CC-Link IE TSN Class
Set the CC-Link IE TSN Class of the device for each slave station.
Setting range
• Number of points: 4 to 8192
• Start: 0H to 1FFCH
• End: 3H to 1FFFH
(Default: Varies depending on the set module)
• Number of points: 16 to 32768
• Start: 0H to 7FF0H
• End: FH to 7FFFH
(Default: Varies depending on the set module)
• Number of points: 1 to 16384
• Start: 0H to 3FFFH
• End: 0H to 3FFFH
(Default: Varies depending on the set module)
• Checked: Distribute parameters
• Not checked: Do not distribute parameters
(Default: Not checked)
0.0.0.1 to 223.255.255.254 (00.00.00.01 to
DF.FF.FF.FE)
(Default: The first to third octets have the
same values as the master station, the fourth
octet has a serial number from 1 to 254)
• 0.0.0.1 to 255.255.255.255 (00.00.00.01 to
FF.FF.FF.FF)
• Empty
*5
(Default: empty
)
• 0.0.0.1 to 223.255.255.254 (00.00.00.01 to
DF.FF.FF.FE)
• Empty
(Default: empty)
• No Setting
• Reserved Station
• Error Invalid Station
(Default: No setting, master station is fixed as
empty)
• Synchronous
• Asynchronous
(Default: Asynchronous)
• Basic Period
• Normal-Speed
• Low-Speed
(Default: Basic Period)
Up to 32 one-byte characters (one-byte or
two-byte)
(Default: empty)
Up to 32 one-byte characters (one-byte or
two-byte)
(Default: empty)
The setting varies depending on the set
module.
*4
• CC-Link IE TSN Class B
• CC-Link IE TSN Class A
(Default: Varies depending on the device)
2 PARAMETER SETTINGS
2.5 "CC-Link IE TSN Configuration" Window
2
119