Error
Error definition and causes
code
3013H
The value set in "Transient Transmission
Time" in "Communication Period Setting"
under "Basic Settings" of the master station
is smaller than the transient transmission
time calculated using the number of slave
stations and the points of slave stations set
in "Network Configuration Settings" under
"Basic Settings".
3014H
When "Communication Mode" under
"Application Settings" of the master station is
set to "Multicast", in the "Network
Configuration Settings" of the "Basic
Settings", "Communication Period Setting" of
the local station is set to "Normal-Speed" or
"Low-Speed".
3015H
Any of the items in the module which is set
as a synchronization target in "Inter-module
Synchronization Setting" in "System
Parameter" are set as follows.
• For a local station in which "Network
Synchronous Communication" in "Network
Configuration Settings" of "Basic Settings"
is set to "Synchronous", "Communication
Period Setting" is set to the setting other
than "Basic Period".
• For "Inter-module Synchronization
Setting" in "System Parameter", a master/
local module mounted to an extension
base unit is set as a synchronization target
module.
3016H
When "Network Topology" under "Basic
Settings" of the master station is set to
"Ring", for "Connection Device Information"
under "Basic Settings", "CC-Link IE TSN
Class Setting" is set to "Mixture of CC-Link
IE TSN Class B/A or CC-Link IE TSN Class
A Only".
3017H
"0.05ms Unit Setting" of "Fixed Scan Interval
Setting of Inter-module Synchronization"
under "Inter-module Synchronization
Setting" in "System Parameter" is set to "Not
Set".
3018H
• A network module with the firmware
version in which the use of multiple
modules as inter-module synchronization
targets is not allowed is used.
• A module which is set as a
synchronization target in "Inter-module
Synchronization Setting" in "System
Parameter" is not set as an inter-module
synchronous master.
• Two master/local modules or more are set
for "Select Inter-module Synchronization
Target Module" under "Inter-module
Synchronization Setting" in "System
Parameter".
4 TROUBLESHOOTING
210
4.5 List of Error Codes
Action
Set "Communication Period Interval Setting" and "Cyclic Transmission
Time" so that the value of "Transient Transmission Time" in "Communication
Period Setting" under "Basic Settings" of the master station is equal to or
larger than the value shown in the detailed information of module
diagnostics.
• Set "Communication Mode" in "Application Settings" of the master station
to "Unicast".
• In "Network Configuration Settings" under "Basic Settings" of the master
station, set "Communication Period Setting" of the local station to "Basic
Period".
Correct the parameters shown in cause.
• Set "Network Topology" of "Basic Settings" of the master station to "Line/
Star".
• For "Connection Device Information" under "Basic Settings" of the master
station, set "CC-Link IE TSN Class Setting" to "CC-Link IE TSN Class B
Only".
Set "0.05ms Unit Setting" of "Fixed Scan Interval Setting of Inter-module
Synchronization" under "Inter-module Synchronization Setting" in "System
Parameter" to "Set".
• Update the firmware version to "11" or later.
• Set the module which is set as a synchronization target in "Inter-module
Synchronization Setting" in "System Parameter" as an inter-module
synchronous master.
• Set only one master/local module for "Select Inter-module
Synchronization Target Module" under "Inter-module Synchronization
Setting" in "System Parameter".
Detailed
information 1
Detailed
information 2
■
■Communication
Period Interval
Information
• Transient
Transmission
Time (Calculation
value: s)
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■Target station
information
• Station Number
• IP address
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■