Error
Error definition and causes
code
300BH
The Announce frame send cycle parameter
error was detected.
300CH
A propagation delay send cycle parameter
error was detected.
300DH
The Sync frame send cycle parameter error
was detected.
300EH
The set values of the master station and
local station do not match.
300FH
Multiple master stations were detected in the
network.
3010H
The value set in "Communication Period
Interval Setting" in "Communication Period
Setting" under "Basic Settings" of the master
station is smaller than the communication
cycle interval calculated by the number of
stations and points of slave stations that was
set in "Network Configuration Settings"
under "Basic Settings".
3011H
The value set in "Cyclic transmission time" in
"Communication Period Setting" under
"Basic Settings" of the master station is
smaller than the cyclic transmission time
calculated by the number of stations and
points of slave stations set in "Network
Configuration Settings" under "Basic
Settings".
3012H
The RJ71GN11-T2 not compatible with
network synchronous communication is set
as the master station, and "Network
Synchronous Communication" in the slave
station in "Network Configuration Settings"
under "Basic Settings" of the master station
is set to "Synchronous".
Action
• Check the Announce frame send cycle parameter setting value of the
device operating as the grandmaster. When the RJ71GN11-T2 is
operating as the grandmaster, reset the CPU module, and run it again.
• If the same error occurs again even after taking the above measure, the
possible cause is a hardware failure of the module. Please consult your
local Mitsubishi representative.
• Check the propagation delay send cycle parameter setting value of the
device operating as the grandmaster. When the RJ71GN11-T2 is
operating as the grandmaster, reset the CPU module, and run it again.
• If the same error occurs again even after taking the above measure, the
possible cause is a hardware failure of the module. Please consult your
local Mitsubishi representative.
• Check the Sync frame send cycle parameter setting value of the device
operating as the grandmaster. When the RJ71GN11-T2 is operating as
the grandmaster, reset the CPU module, and run it again.
• If the same error occurs again even after taking the above measure, the
possible cause is a hardware failure of the module. Please consult your
local Mitsubishi representative.
Set the same parameter setting values for "Network No." and "Station No."
of the local station to the setting values of the master station.
• Connect only one master station on the same network.
• After taking the above action, power off and on or reset all stations where
the error was detected.
Set the value of "Communication Period Interval Setting" over the value in
the detailed information displayed by module diagnostics using
"Communication Period Setting" under "Basic Settings" of the master
station.
If the detailed information value exceeds the upper limit of "Communication
Period Interval Setting" that can be set in the master station, reduce the
number of modules connected to the master station and the number of link
devices assigned to each module in "Network Configuration Settings", so
that the upper limit of "Communication Period Interval Setting" is not
exceeded.
Set the value of "Cyclic Transmission Time" over the value in the detailed
information displayed by module diagnostics using "Communication Period
Setting" under "Basic Settings" of the master station.
If the detailed information value exceeds the upper limit of "Cyclic
Transmission Time" that can be set in the master station, reduce the number
of modules connected to the master station and the number of link devices
assigned to each module in "Network Configuration Settings", so that the
upper limit of "Communication Period Interval Setting" is not exceeded.
• Update the firmware version to "11" or later.
• In "Network Configuration Settings" under "Basic Settings" of the master
station, set "Network Synchronous Communication" of the slave station to
"Asynchronous".
Detailed
information 1
Detailed
information 2
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
• Network No.
• Station No.
■
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■Overlapped type
information
• 5: Master station
duplication
■
■Communication
Period Interval
Information
• Communication
Period Interval
(Calculation
value: s)
■
■Communication
Period Interval
Information
• Cyclic
Transmission
Time (Calculation
value: s)
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■
4 TROUBLESHOOTING
209
4.5 List of Error Codes
4