Error
Error definition and causes
code
DA00H
An error was detected in the network
module.
DA10H
An error was detected in the network
to
module.
DA17H
DA19H
An error was detected in the network
module.
DA1AH
After parameters were set using the
CCPASETX instruction/CCPASET
instruction, the CCPASETX instruction/
CCPASET instruction were executed again.
DA1BH
A dedicated instruction which the target
station does not support was executed.
DA1CH
The target station of the READ/SREAD/
WRITE/SWRITE/SEND/REQ instruction
does not exist.
DB00H
The station numbers of 121 stations or more
are specified.
DC00H
The setting value is incorrect.
DC01H
The setting value was not written correctly.
Action
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Parameter setting with the CCPASETX instruction is limited to one time only.
Execute the instruction again after resetting the CPU module.
• Change the target station at the station that executed the READ/SREAD/
WRITE/SWRITE/SEND/REQ instruction.
• Correct the network number and station number/IP address of the target
station of the dedicated instruction.
If the target station of the READ/SREAD/WRITE/SWRITE/SEND/REQ
instruction is disconnected, execute the dedicated instruction again after
return of the target station.
Check station numbers.
Execute the write instruction again after correcting the setting value.
Execute the write instruction again. Please consult your local Mitsubishi
representative.
Detailed
information 1
Detailed
information 2
4 TROUBLESHOOTING
231
4.5 List of Error Codes