Item
RWr/LW
Source
LW/RWw
Destination
Link devices set for "Source" can be overlapped. Doing so will allow transfer of the same link devices to
multiple network modules.
Precautions
■Modules that can support interlink transmission
• RJ71GN11-T2 (master station)
• CC-Link IE Controller Network-equipped module (control station, normal station)
• CC-Link IE Field Network-equipped module (master station and submaster station)
• RJ71LP21-25 (control station and normal station)
■Transfer destination link device setting
Do not use link devices set for link refresh range as a transfer destination. If doing so, transfer destination link devices will be
overwritten by link refresh. To use transfer destination link device data in the CPU module, set the transfer source link device
as the link refresh range.
CPU module
Link refresh
range 1
Link refresh
range 2
2 PARAMETER SETTINGS
114
2.4 Application Settings
Description
Enter the link device range of the transfer source and destination modules. Up to 64 interlink
transmission ranges can be set. RWr and RWw points can be assigned in increments of 4.
No.1
RWr
LW
No.2
LW
RWr
·
·
·
No.64
LW
RWr
Network
module 1
No.1
LW
RWw
No.2
RWw
LW
·
·
·
No.64
RWw
LW
Network
module 2
Transfer
source
Setting range
RWr: 0H to 1FFFH
RWw: 0H to 1FFFH
(Default: empty)