Mitsubishi Electric MELSEC iQ-R Series User Manual page 285

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

No.
Name
Description
SW01C8 to
Synchronous/
Stores the information about operating status of the CC-Link IE TSN Network
SW01CF
asynchronous
synchronous communication function for each station.
operating status
0: Asynchronous setting
information of
1: Synchronous setting
each station
Stations which are not executing an inter-module synchronous interrupt program
because the CPU operating status is currently STOP or PAUSE (the status under
which the program cannot be executed) are also treated as asynchronous setting
(0).
SW01C8
SW01C9
SW01CA
SW01CB
SW01CC
SW01CD
SW01CE
SW01CF
Each number in the table represents a station number.
 is fixed to 0.
(Conditions)
• Stations that surpass the maximum station number are ignored.
SW01D0 to
Watchdog
Stores the watchdog counter operating status information for each station in CC-
SW01D7
counter
Link IE TSN communications. (Station number: 1 to 120)
operating status
0: Not operating
information for
1: Operating
each station
Stations which are not performing data links are treated as "0: Not operating"
because the information indicates that slave stations are communicating using
the watchdog counter.
SW01D0
SW01D1
SW01D2
SW01D3
SW01D4
SW01D5
SW01D6
SW01D7
Each number in the table represents a station number.
 is fixed to 0.
(Conditions)
• Stations that surpass the maximum station number are ignored.
SW01E9
Inter-module
Indicates the number of times cyclic data transfer processing is not completed
synchronization
within the inter-module synchronization cycle. The status is cleared by powering
cycle over count
off and on the system or by resetting the CPU module.
0: Cycle over not occurred
1 to 65535: Cumulative number of times
When FFFFH (maximum value 65535) is counted, counting stops.
SW01EA to
Inter-module
Stores the cycle setting value of the fixed interval synchronization of Inter-module
synchronization. (Unit: s)
SW01EB
synchronization
cycle setting
"0" is stored when the inter-module synchronization function is not used.
value
SW025A
Remote device
Stores the request result of 'Remote device forced output request' (SB0016).
forced output
0: Normal
request result
1 or greater: Not completed
If not completed, an error code is stored.
When 'Remote device forced output request' (SB0016) is turned off, the stored
error code is cleared.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
16 15 14 13 12 11 10
9
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
120 119 118 117 116 115 114 113
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
16 15 14 13 12 11 10
9
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
120 119 118 117 116 115 114 113
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
Appendix 5 List of Link Special Register (SW)
Availability
Master
Local station
station
Unicast
Multicast
mode
mode
APPX
A
283

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r cc-link ie tsn

Table of Contents