Chapter 4 • Hydran 201Ti's Displays and Menus
Use this submenu only to install a new H201 sensor, because it
WARNING
CAUTION
changes the Service;ServiceData parameters. These parameters are
used to evaluate the state of the H201 sensor.
4.5.9

Calibration Submenu (Extended Menu Only)

The Calibration submenu is used to calibrate:
• The three analog inputs:
– The Hydran 201 sensor signal
– The H201 sensor temperature
– The heating plate temperature
• The analog output
This command requires password No. 2.
If you go further than the CalibrateNow? message in this submenu,
WARNING
CAUTION
the calibration is destroyed.
There are five branches in this submenu:
• LowRange: Calibration of the H201 sensor signal's low range.
• HighRange: Calibration of the H201 sensor signal's high range.
• SensorTemp: Calibration of the H201 sensor temperature.
• HeaterTemp: Calibration of the heating plate temperature.
• SignAnalog: Calibration of the analog output.
4-26
Rev. 6, March 2011
Part 17997